Undervoltage monitoring for 3-phase mains with fixed threshold voltage and fi xed hysteresis. All measuring inputs (L1, L2 and L3) must be connected to phase voltage. If single or 2-phase monitoring is required, unused input terminals (L) must be connected to mains voltage to have proper L-N voltage on the terminals L1, L2 and L3. If there is a reverse voltage on account of a consumer, which exeeds the fixed threshold, detection of phase failure isn't possible.
Undervoltage monitoring with ON delay (Option E)
When the voltage of all connected phases exeeds the fixed threshold by more than the fixed hysteresis, the set interval t begins (green LED U/t flashes). After the set interval t has expired, the output relay R switches into on-position (yellow LED R illuminated, green LED U/t illuminated). When the voltage of one of the connected phases falls below the fixed threshold, the output relay R switches into off-position (yellow LED R not illuminated, green LED U/t not illuminated).
Modular devices (PDF datasheet)Product enquiry and further information (Contact us form)
AC/DC undervoltage monitoring in 1-phase mains with adjustable threshold and fixed hysteresis.
The supply voltage U must be constantly applied to the device (green LED illuminated).
The output relay R switches into on-position (yellow LED illuminated) when the measured voltage U exceeds the value adjusted at the Usregulator. The output relay R switches into off-position (yellow LED not illuminated) when the measured value for the voltage falls below the set value by more than the fixed hysteresis.
Modular devices (PDF datasheet)Product enquiry and further information (Contact us form)
Undervoltage monitoring in 3-phase mains (each phase against the neutral wire) with fixed or variable threshold voltage US and fixed hysteresis.
Modular devices (PDF datasheet)Product enquiry and further information (Contact us form)
Temperature monitoring of the motor winding (max. 6 PTC) with fault latch for temperature sensors in accordance with DIN 44081, short circuit monitoring of the thermistor line (selectable by means of terminals), integrated test/reset key.
Temperature monitoring of the motor winding with fault latch. If the supply voltage U is applied (green LED illuminated) and the cumulative resistance of the PTC-circuit is less than 3.6kΩ (standard temperature of the motor), the output relay switches into on-position. Pressing the test/reset key under this conditions forces the output relay to switch into off-position. It remains in state as long as the test/reset key is pressed and thus the switching function can be checked in case of fault. The test function is not effective by using an external reset key. When the comulative resistance of the PTC-circuit exceeds 3.6kΩ(at least one of the PTCs has reached the cut-off temperature), the output relay switches into off-position (red LED illuminated). The output relay switches into on-position again (red LED not illuminated), if the cumulative resistance drops below 1.6Ω5k by cooling down of the PTC and either a reset key (internal or external) was pressed or the supply voltage was disconnected and re-applied.
Modular devices (PDF datasheet)Product enquiry and further information (Contact us form)
Level monitoring of conductive liquid, timing for tripping delay and turn-off delay seperatly adjustable and the following functions (selectable by means of rotary switch):
Connection of the probe rods E1, E2 and E3. Alternatively the electrically conducting container can be connected in lieu of the test probe E3. When the air-fluid level falls below the minimum probe E2 the set interval of tripping delay (Delay ON) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the maximum probe E1, the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated).
Connection of the probe rods E1, E2 and E3. Alternatively the electrically conducting container can be connected in lieu of the test probe E3. When the maximum probe E1 gets moistened the set interval of tripping delay (Delay ON) begins. After the expiration of the interval the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level falls below the minimum probe E2, the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval, the output relays R switches into offposition (yellow LED not illuminated).
Connection the probe rods E2 and E3 (bridge E1-E3). Alt-er natively the electrically conducting container can be connected in lieu of the test probe E3. When the air-fluid level falls below the probe E2 the set interval of tripping delay (Delay ON) begins. After the expiration of the interval, the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level again rises above the probe E2, the set interval of turnoff delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated).
Connection of probe rods E2 and E3 (bridge E1-E3). Alternatively the electrically conducting container can be connected in lieu of the test probe E3. When the probe E2 gets moistened the set interval of tripping delay (Delay ON) begins. After the expiration of the interval the output relays R switches into on-position (yellow LED illuminated). When the air-fluid level sinks below the probe E2, the set interval of turn-off delay (Delay OFF) begins. After the expiration of the interval the output relays R switches into off-position (yellow LED not illuminated).
Modular devices (PDF datasheet)
Product enquiry and further information (Contact us form)
AC current monitoring in 1-phase mains with adjustable threshold and fixed hysteresis.
The supply voltage U must be constantly applied to the device (green LED illuminated). The output relay R switches into on-position (yellow LED illuminated) when the measured current exceeds the value adjusted at the Isregulator. The output relay R switches into off-position (yellow LED not illuminated) when the measured value for the current falls below the set value by more than the fixed hysteresis.
Modular devices (PDF datasheet)Product enquiry and further information (Contact us form)
Monitoring of phase sequence, phase failure and asymmetry with adjustable asymmetrie, connection of neutral wire optional.
When all the phases are connected in the correct sequence and the measured asymmetry is less than the fixed value, the output relay switches into on-position (yellow LED illuminated). When the phase sequence changes, the output relay switches into off-position (yellow LED not illuminated).
The output relay R switches into off-position (yellow LED not illuminated) when the asymmetrie exceeds the value set at the ASYM-regulator. Reverse voltages of a consumer (e.g. a motor which continues to run on two phases only) do not effect the disconnection.
The output relay switches into off-position (yellow LED not illuminated), when one of the three phases fails.