R1120 - Temperature Controller
      
      Clarian R1120 (PDF datasheet). Product enquiry and further information (Contact us form).
      
      The R1120 PID controller features a sophisticated control function. All essential settings are shown on the two 7-segment displays and are easily adjusted using the rotary switch. The 2-point or 3-point controller is also available as a variant with 3-point step control. Further feature. With an optional seal the housing front can achieve a protection class of IP54. Further characteristics: Self-optimising 
Technical Data
      
        
          
            Input Thermocouple:
            
              -  Built-in internal compensation point and protection against sensor break and incorrect polarity.
-  Re-calibration not required for a line resistance of up to 50 ohm.
-  Calibration accuracy: < 0,25 %
 Input RTD, Pt 100 (DIN):
            
              -  2- or 3-wire connection possible.
-  Built-in protection against sensor break and short circuit. 
- Max. permissible line resistance by 3-wire connection: 80 ohm 
- Sensor current: < 0,5 mA 
- Calibration accuracy: < 0,2 % 
Linear error: 
            
 Influence of the ambient temperature: 
            
OUT 1: 
            
              - R1120-10?: Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load) 
- R1120-20?: bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof 
OUT 2:
            
              -  Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load) 
OUT 3: 
            
              - Relay, (n/o contact) max. 250 V AC, max. 3 A (resistive load) 
7-Segment-Display: 
            
              - Process: 10 mm red, Set: 10 mm red 
 
         
        
          
            Data protection:
            
            CE-mark: 
            
              - EMC: 2004/108/EC, EN 61326-1 for industrial areas 
- EN 61010-1 
Power supply: 
            
              - Standard: 230 V AC, ± 10 %, 48...62 Hz 
Connections: 
            
              - Plug-in screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C 
Permissible operating conditions:
            
              -  Operating temperature: 0...50 °C / 32...122 °F 
- Storage temperature: -30...70 °C / -22...158 °F 
- Climate class: KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation
 Casing: 
            
              - Format: 96 x 96 mm (DIN 43700), installation depth 67 mm
-  Panel cutout: 92 +0,5 mm x 92 +0,5 mm 
- Material: Noryl, self-extinguishing, non-drip, UL 94-V1
-  Protection mode: IP 20 (DIN 40050), IP 50 front side
 Further feature:
            
              - With an optional seal the housing front can achieve a protection class of IP54. 
Further characteristics: 
Weight: 
            
            Subject to technical improvements.