R 2500 - 4 / 10 / 12 / 16 controller zones
The multi-zone temperature controller R2500 is available with up to 16 control zones. It displays control functions and all key information clearly on its large screen. The modular device can be equipped optionally with different fieldbus interfaces. For international use, the appliance can be operated with 230 V 50 Hz, 115 V 50-60 Hz, 24 V 50-60 Hz and 24 VDC.
- Multizones (multiloop) Temperature Controller with LCD-Display
- Controlling and monitoring of 8, 10, 12 or 16 temperature zones.
- The basic contruction of the new multizones
controller R2400 is similar to the relaible R2100 controller.
Therefore it´s dimensions, general functions and terminals are compatible to the R2100.
- The blue LCD-display is very significant for the new controller.
- With the help of two menues and software controlled function keys it allows a better operation.
- A builtin recorder function allowes the diagnostic
of the process value course.
Clarian R2500 (PDF datasheet). Product enquiry and further information (Contact us form).
Product Specification
Input PT100 (RTD)
- 2- or 3- wire connection possible
- Built-in protection against sensor breakage and short circuit
- Sensor current: … < 1 mA
- Calibration accuracy: … < 0,2 % Linear error: … < 0,2 %
- Influence of the ambient temperature: … < 0,01 % / K
Input Thermocouple
- Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
- Re-calibration not required for a line resistance of up to 50 Ohm.
- Calibration accuracy: … < 0,25 % Linear error: … < 0,2 %
- Influence of the ambient temperature: … < 0,01 % / K
External contacts
- Designed for connecting external potential-free contacts. The contact voltage (approx. 24 V DC, max. 1mA) is provided at controller terminal 75.
Heater current monitoring
- Measuring input range: 0 … 100mA corresponding 0,0 … 99,9A when using a current transformer 1:1000.
- If the value of 100mA is exceeded, the controller may be damaged.
Control outputs
- Bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof or Relay, max. 250 VAC, max. 3 A (resistive load)
Alarm outputs
- Relay, max. 250 VAC, max. 3 A (resistive load)
LCD-Display
- Blue STN-display with permanent, white LED-backlight
- Graphic: 240 x 64 pixel
- Text: 8 lines with 40 characters each
Data protection
- EAROM
- When using a Fieldbus interface please note: Permissible writing operations per parameter must not exceed 1 000 000.
CE-mark
- Tested according to 2004/108/EG; EN 61326-1
- Electrical safety: EN 61010-1
Power supply
- Depends on the version of the device:
- 230 V AC, +/-10 %, 48 … 62 Hz; approx. 10VA
- 115 V AC, +/-10 %, 48 … 62 Hz; approx. 10VA
- 24 V DC, +/-25 %, approx. 10W
Connections
- Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C
Permissible operating conditions
- Operating temperature:
- Storage temperature:
- Climate class:
- KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation
Casing
- Format, case:
- 192x96mm, (DIN 43700), installation depth 122 mm
- Panel cutout:
- Format, face plate:
- Material:
- Noryl, self-extinguishing, non-drip, UL 94-V1
- Protection mode:
- IP 20 (DIN 40050), IP 50 front side
Weight
- Approx. 800g … 1100g, depends on the version of the device
Fieldbus Interface (optically isolated)
- Depends on the version of the device:
- Serial: RS232, RS485, TTY (20mA) Elotech protocol, Modbus RTU
- CANopen, CiA Device Profile DS-404
- Profibus DP, according to EN 50170
Service Interface (Option):
Subject to technical improvements.