Technical Data

Input RTD, Pt 100 (DIN):

  • 2 - or 3 - wire connection possible.
  • Built-in protection against sensor breakage and short circuit.
  • Max. permissible line resistance by 3-wire connection: 80 Ohms
  • Sensor current: < 1 mA
  • Calibration accuracy: < 0,2 %
  • Linear error: < 0,2 %
  • Influence of the ambient temperature: < 0,01 % / K

Input Thermocouple:

  • Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
  • Re-calibration not required for a line resistance of up to 50 Ohms.
  • Calibration accuracy: < 0,25%

Analog inputs (Option):

  • 0 ... 10 V DC (Display range programmable)

Setpoint selection:

  • Ext. potential-free contact, switching voltage appr. 24 V DC, max. 1 mA.
  • Selection between SP1 and SP2 valid for all zones.

Control outputs OUT 1 ... OUT 8:

  • Bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof

Alarm outputs A1 and A2:

  • Relay, max. 250 V AC, max. 3 A (cos-phi = 1)

7-Segment-Display:

  • Process: 10 mm red, Set: 10 mm red

Data protection:

  • EAROM

CE-Mark

  • Tested according to 2004/108/EC; EN 61326-1; industrial areas
  • Electr. safety: EN 61010-1

Power supply:

  • 115 / 230 / 24 V AC: ± 10%, 48...62 Hz; appr. 10VA 24 V DC: +/-25%

Connections:

  • Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C

Permissible operating conditions:

  • Operating temperature: 0...50 °C / 32...122 °F
  • Storage temperature: -30...70 °C / -22...158 °F
  • Climate class: KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation

Casing:

  • Format: 96 x 96 mm (DIN 43700), installation depth 122 mm
  • Panel cutout: 92 +0,5 mm x 92 +0,5 mm
  • Material: Noryl, self-extinguishing, non-drip, UL 94-V1
  • Protection mode: IP 20 (DIN 40050), IP 50 front side

Weight:

  • app. 800 g

Heater current monitoring:

  • Current transformer 1:1000:
    (Type M2000)
    • Passive through current transformer with snap-in attachment for DIN rail mounting (EN 50022, 35mm).
    • Connections to the controller: 2 x 6,3mm flat connectors.
  • Heater current detection and indication range:
    • 0...max. 60,0A. Single-phase operation.
    • 0...max. 99,9 A. Three-phase operation.
    • The sum of the current of all three phases of one controller zone will be monitored.
    • Variations of the power supply voltage have to be considered when the the alarm values are programmed.
  • Current detection interval time programmable (1...60 sec.).
    • This is the time between the measuring of two successive controller zones.
  • Alarm delay time programmable.
    • It depends upon the current detection interval time and the number of the connected temperature zones (min. 8 sec.).

 

Subject to technical improvements