R 2200 - 4 / 6 / 8 / 10 / 16 controller zones

R 2200 - 4 / 6 / 8 / 10 / 16 controller zones

Clarian R2200 (PDF datasheet).Product enquiry and further information (Contact us form).

The ultimate device for control cabinet installation with 4-16 control zones. Data interfaces RS 232, RS 485 inclusive, optionally available also with CAN, Profibus and service interface.

  • Networkable and remote control-capable with service interface

Product Specification

Input PT100 (RTD)

  • 2- or 3- wire connection possible
  • Built-in protection against sensor breakage and short circuit
  • Sensor current: … < 1 mA
  • Calibration accuracy: … < 0,2 % Linear error: … < 0,2 %
  • Influence of the ambient temperature: … < 0,01 % / K

Input Thermocouple

  • Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
  • Re-calibration not required for a line resistance of up to 50 Ohm.
  • Calibration accuracy: … < 0,25 % Linear error: … < 0,2 %
  • Influence of the ambient temperature: … < 0,01 % / K

External contacts

  • Designed for connecting external potential-free contacts. The contact voltage (approx. 24 V DC, max. 1mA) is provided at controller terminal 75.

Heater current monitoring

  • Measuring input range: 0 … 100mA corresponding 0,0 … 99,9A when using a current transformer 1:1000.
  • If the value of 100mA is exceeded, the controller may be damaged.

Control outputs

  • Bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof or Relay, max. 250 VAC, max. 3 A (cos-phi = 1)

Alarm outputs

  • Relay, max. 250 VAC, max. 3 A (cos-phi = 1)

Data protection

  • EAROM
  • When using a Fieldbus interface please note: Permissible writing operations per parameter must not exceed 1 000 000.

CE-mark

  • Tested according to 2004/108/EG; EN 61326-1
  • Electrical safety: EN 61010-1

Power supply

  • Depends on the version of the device:
    • 230 V AC, +/-10 %, 48 … 62 Hz; approx. 7 VA
    • 115 V AC, +/-10 %, 48 … 62 Hz; approx. 7 VA
    • 24 V DC, +/-25 %, approx. 7 W

Connections

  • Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C

Permissible operating conditions

  • Operating temperature:
    • 0 … 50°C / 32 … 122°F
  • Storage temperature:
    • -30 … 70°C / -22 … 158°F
  • Climate class:
    • KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation

Casing

  • Case for DIN-rail mounting (35mm symetric, EN 50 022)
  • Dimensions: 125mm x 105mm x 125mm
  • Material: Polycarbonat (PC)
  • Protection mode: IP 20 (DIN 40050)

Weight

  • Approx. 800g, depends on the version of the device

Fieldbus Interface (optically isolated)

  • Depends on the version of the device:
    • Serial: RS232, RS485, TTY (20mA)
    • CANopen, CiA Device Profile DS-404
    • Profibus DP, according to EN 50170

Service-Interface

  • RS485, 115,2 kbaud, 8N1

Subject to technical improvements.

Product enquiry and further information

We would be delighted to offer free application advice, technical information on products, free quotations and delivery information.

Name

Telephone

Product enquiry & further information