R 2000N - The economy model

R 2000 - 4 / 6 / 8 / 10 controller zones

Clarian R2000N (PDF datasheet). Product enquiry and further information (Contact us form).

Multi-zone temperature controller for 4 zones

Technical Data

Input PT100 (RTD)

  • 2- or 3- wire connection possible
  • Built-in protection against sensor breakage and short circuit
  • Sensor current: … < 1 mA
  • Calibration accuracy: … < 0,2 % Linear error: … < 0,2 %
  • Influence of the ambient temperature: … < 0,01 % / K

Input Thermocouple

  • Built-in internal compensation point and protection against sensor breakage and incorrect polarity.
  • Re-calibration not required for a line resistance of up to 50 Ohm.
  • Calibration accuracy: … < 0,25 % Linear error: … < 0,2 %
  • Influence of the ambient temperature: … < 0,01 % / K

External contacts

  • Designed for connecting external potential-free contacts. The contact voltage (approx. 24 V DC, max. 1mA) is provided at controller terminal 75.

Heater current monitoring

  • Measuring input range: 0 … 100mA corresponding 0,0 … 99,9A when using a current transformer 1:1000.
  • If the value of 100mA is exceeded, the controller may be damaged.

Control outputs

  • Bist. voltage signal, 0/18 V DC, max. 10 mA, short-circuit proof or Relay, max. 250 VAC, max. 3 A (cos-phi = 1)

Alarm outputs

  • Relay, max. 250 VAC, max. 3 A (cos-phi = 1)

7-Segment-Display:

  • Process: 10 mm red, Set: 10 mm red

Data protection

  • EAROM
  • When using a Fieldbus interface please note: Permissible writing operations per parameter must not exceed 1 000 000.

CE-mark

  • Tested according to 2004/108/EG; EN 61326-1
  • Electrical safety: EN 61010-1

Power supply

  • Depends on the version of the device:
    • 230 V AC, +/-10 %, 48 … 62 Hz; approx. 10VA
    • 115 V AC, +/-10 %, 48 … 62 Hz; approx. 10VA
    • 24 V DC, +/-25 %, approx. 10W

Connections

  • Screw terminals, Protection mode IP 20 (DIN 40050), Insulation class C

Permissible operating conditions

  • Operating temperature:
    • 0 … 50°C / 32 … 122°F
  • Storage temperature:
    • -30 … 70°C / -22 … 158°F
  • Climate class:
    • KWF DIN 40040; equivalent to annual average max. 75 % rel. humidity, no condensation

Casing

  • Format, case:
    • ¼-DIN; 96 x 96 mm (DIN 43700), installation depth 122 mm
  • Panel cutout:
    • 92 +0,5 mm x 92 +0,5 mm
  • Material:
    • Noryl, self-extinguishing, non-drip, UL 94-V1
  • Protection mode:
    • IP 20 (DIN 40050), IP 50 front side

Weight

  • Approx. 800g, depends on the version of the device

Fieldbus Interface (optically isolated)

  • Depends on the version of the device:
    • Serial: RS232, RS485, TTY (20mA)

Subject to technical improvements

Product enquiry and further information

We would be delighted to offer free application advice, technical information on products, free quotations and delivery information.

Name

Telephone

Product enquiry & further information